The design and experimental validation of an emergency core cooling system for a pool type research reactor

Carregando...
Imagem de Miniatura

Data

Data de publicação

2017

Orientador

Título da Revista

ISSN da Revista

Título do Volume

É parte de

É parte de

É parte de

É parte de

60 YEARS OF IEA-R1: INTERNATIONAL WORKSHOP ON UTILIZATION OF RESEARCH REACTORS
Exportar
Mendeley

Projetos de Pesquisa

Unidades Organizacionais

Fascículo

Resumo
This paper presents the design of the Emergency Core Cooling System (ECCS) for the IEA-R1 pool type research reactor. This system, with passive features, uses sprays installed above the core. The experimental program performed to define system parameters and to demonstrate to the licensing authorities, that the fuel elements limiting temperature is not exceeded, is also presented. Flow distribution experiments using a core mock-up in full scale were performed to define the spray header geometry and spray nozzles specifications as well as the system total flow rate. Another set of experiments using electrically heated plates simulating heat fluxes corresponding to the decay heat curve after full power operation at 5 MW was conducted to measure the temperature distribution at the most critical position. The observed water flow pattern through the plates has a very peculiar behavior resulting in a temperature distribution which was modeled by a 2D energy equation numerical solution. In all tested conditions, the measured temperatures were shown to be below the limiting value.

Como referenciar
TORRES, W.M.; BAPTISTA, B.D.; TING, D.K.S. The design and experimental validation of an emergency core cooling system for a pool type research reactor. In: 60 YEARS OF IEA-R1: INTERNATIONAL WORKSHOP ON UTILIZATION OF RESEARCH REACTORS, November 28 - December 01, 2017, São Paulo, SP. Abstract... São Paulo, SP: Instituto de Pesquisas Energéticas e Nucleares, 2017. p. 62-62. Disponível em: http://repositorio.ipen.br/handle/123456789/28761. Acesso em: 30 Dec 2025.
Esta referência é gerada automaticamente de acordo com as normas do estilo IPEN/SP (ABNT NBR 6023) e recomenda-se uma verificação final e ajustes caso necessário.